CCC Program - Minimum Clearances For
Backflow Prevention Assemblies

Assembly 2 INCHES AND SMALLER:

Install with a minimum of 6 inches clearance in all directions around the assembly.

Assembly 2 ½ INCHES AND LARGER:

Install with a minimum of 12 inches clearance in all directions around the assembly and a minimum of 24 inches of clearance in front of the assebly, where testing and repair are performed.

PRESSURE VACUUM BREAKERS (PVB):

Must meet the additional requirement of 12 inches above the highest point of water use downstream of the backflow preventer.